Fire 2024, 7(12), 486; https://doi.org/10.3390/fire7120486 (registering DOI)
Submission received: 26 August 2023 / Revised: 19 September 2023 / Accepted: 17 June 2024 / Published: 23 December 2024
(This article belongs to the Special Issue Compartment Fire and Safety)

1. Introduction

The number of big fires in buildings appears to be increasing [1]. People are occupying compartments in buildings in dense urban areas and enclosed spaces such as train cars. As the number of fires—including arson and terrorist attack fires—appears to be increasing in recent decades, compartment fire safety must be carefully considered. Fundamental scientific research on flashovers for different room fires will lead to the development of more appropriate firefighting strategies. The room fire scenarios that lead to more extensive fires and their associated changes in compartment fire characteristics, including the fuel mass loss rate and flame characteristics of the operating system, are exciting topics for further study.
This Special Issue was proposed with an aim of achieving a better scientific understanding of room fires under different ventilation conditions. Different aspects of fire science in the area of compartment fire research, such as burning regimes, flame patterns, flashover, etc., can be updated to match new styles of living and travel. The latest developments in compartment fire and safety, in addition to the possible fire protection implications for associated regulations and standards, are presented.
In this Special Issue on compartment fire and safety, a number of important topics were covered by contributions from colleagues in different countries, including Australia, Cameroon, Mainland China, Hong Kong, Taiwan, France, Korea, and Russia. The topics investigated include the burning of building materials, fire suppression systems, and fire risks in different types of enclosures, including green buildings, high-rise buildings, pressurized buildings, long-term care institutions, and railway tunnels. Parameters of interest span topics such as heat release rates, smoke toxicity, evacuation times, and ventilation velocity.
These research results were obtained using various methods, including experimental, modeling, and simulation, which all add knowledge to the field of compartment fire studies. Topics included the burning characteristics of PE foam blocks used as interior building materials and the effect of coating on retarding fire ignition. The fire hazards of vertical greenery systems were also studied, with the conclusion that in certain conditions, the fire spread could be more rapid compared with external thermal insulation composite systems and double-skin façades. In contrast, the importance of the effect of ventilation was investigated using numerical method. Studies on smoke hazard, a very important factor in compartment fire safety, were reported. Fire detection and suppression were investigated. Compartment fire hazards in specific buildings such as high-rise residential buildings, high-altitude hermetic pressurization buildings, and long-term care institutes were reported.
The results will be applied in drafting fire safety management guidelines for existing buildings with high occupancies. In the long term, fire codes could be drafted for the next generation of buildings. More importantly, fire safety provisions, including fire safety management strategies from compartment fire research, atria, tunnels, tall buildings, underground spaces, mini storage units, transport vehicles, airplanes, ships, and submarines, will be affected.

2. Tall Buildings

New challenges arise from storing too many combustibles in rooms of taller buildings, where both the fire load density and occupant loading are high. New materials, such as fire retardants, flammable clean refrigerants, and environmentally friendly fire suppressants have been developed to satisfy older fire tests. New scenarios for big fires and explosions due to electric batteries and power supplies are not yet included in codes that were developed years ago. New lifestyles with more plastic furniture and glass partition areas lead to more fire and smoke hazards [2]. Protection against flashover fires must be carefully considered. Traditional water suppression systems, particularly automatic sprinkler systems [3], are required by fire authorities to reduce the possibility of uncontrolled fires. However, they are installed to meet earlier fire codes, which might not be able to face these new challenges. Sprinklers will discharge water upon activation to cool the burning objects, prewet walls and floors, cool the smoke layer to reduce the chance of flashover, and displace oxygen away from the burning objects. It is necessary to study how to improve their performance with respect to two key performance parameters in sprinklers: thermal activation and adequate water delivery—not too much, nor too little—particularly for tall and big halls.
This Editorial discusses active systems fighting against big flashover fires. Three systems are presented to address the two important problems of thermal activation and water delivery in active water systems in tall halls [3]. These include long-throw sprinklers [4], water guns [5], and positive pressure ventilation (PPV) blowers [6] to handle hazardous environments.

3. Water Gun Systems

Water guns with an infra-red detection and flame sensor system were used in big halls [5]. An appropriate design can dispense adequate, but not excessive, water. However, in many places, including Hong Kong, water gun systems have not been regarded as approved fire protection systems for protecting tall spaces that do not function as storage areas for years. The situation is starting to change because of the availability of new software and hardware. Whether the water gun system can control a fire [7] must be demonstrated experimentally.
The system is allowed in many places, including Mainland China and Taiwan, and many new water gun products are being developed [8]. Fire authorities are starting to consider using such systems with electronic equipment in several areas.

4. Long-Throw Sprinklers

Sidewall long-throw sprinklers at height are allowed [9] for tall halls that are not used as warehouses. Field tests demonstrated an acceptable water distribution density by adjusting the discharge water jet’s angle [9]. A small wood crib of 20 kg ignited by a 0.6 m diameter pool fire with 1 liter gasoline was tested [9] in a hall. Water was discharged at 273 s, with the fire extinguished at 460 s. The system worked as expected to suppress small fires. However, the complicated air flow pattern due to sprinklers discharging water with fire-induced movement during a big fire is a concern.
Experiments with bigger fires are required to evaluate the performance of long-throw sprinklers at height. Such sprinklers can provide the required water distribution density in the protected coverage areas to acceptable standards.

5. Water Turbine-Driven Positive Pressure Ventilation (PPV) Blower

Installing active fire suppression systems can prevent or delay flashover fires. The fire can also be controlled. However, a huge volume of smoke will be liberated, because the intermediate reactions are stopped. Smoke and toxic gases must be driven out. Operating positive pressure ventilation (PPV) [6,10,11] is necessary. Water turbine-driven PPV blowers with water suppression or water shielding could serve this purpose and are commonly used by firefighters.

6. Computational Fluid Dynamics

Computational Fluid Dynamics (CFD) has been used [12,13,14,15,16,17] in fire hazard assessments in performance-based design (PBD) or the Fire Engineering Approach (FEA) [13,17,18]. A workshop focusing on this was held in 2017 [19]. Discrepancies between experimental data and computational results might be attributed to modeling errors. Poor CFD studies might lead to inadequate protection.
There are general concerns on applying CFD to simulate combustion, even for small fires in big rooms [14,17]. Even burning Poly(methyl methacrylate) (PMMA) with simple kinetics of thermal decomposition [20], there are three stages in the combustion process. Thermal radiative feedback from the ceiling was a significant factor in determining the fuel gasification rate [21]. ‘Bridge-mixing’ of igniting fuel vapors gasified from different combustibles by means of thermal radiation during flashover was observed [22]. The ‘bridge-mixing’ concept was verified by preliminary simultaneous cone calorimetry.
However, there are many disagreements, and studies are needed to complement the preliminary findings [13,17,18]. Fire safety provisions have to be upgraded, if necessary, as in the above-described cases. Fire safety management must at the very least be reviewed [23].

7. Conclusions

Fire safety in tall or big halls always presents challenges to management and firefighters. There are different types of active firefighting systems, each with its merits and limitations. A proper selection of the system requires professional knowledge and experience, as well as the support of stakeholders. The successful integration of the system into the building structure can only be achieved via collaboration of parties from different professions. It is worth mentioning the employment of CFD in assisting with the design of a system, at least in the preliminary stage, as it saves a lot of time and money, although CFD results have to be carefully applied.
Safety aspects should be watched more carefully by responsible actors and top management of organizations. Fire safety must be provided according to regulations. However, the penalty on non-compliance with safety was previously very low in many places (several thousand US dollars, even with casualty). This type of safety culture has changed recently, with more stringent punishments. The demand for recruiting more safety experts with practical experience is expected to be higher. This might create a bigger market for fire safety personnel.

Author Contributions

Conceptualization, C.-L.C., C.-H.C. and W.-K.C.; methodology, C.-L.C., C.-H.C. and W.-K.C.; formal analysis, C.-L.C., C.-H.C. and W.-K.C.; investigation, C.-L.C., C.-H.C. and W.-K.C.; resources, C.-L.C., C.-H.C. and W.-K.C.; data curation, C.-L.C., C.-H.C. and W.-K.C.; writing—original draft preparation, C.-L.C., C.-H.C. and W.-K.C.; writing—review and editing, C.-L.C., C.-H.C. and W.-K.C.; supervision, C.-L.C., C.-H.C. and W.-K.C.; funding acquisition, C.-L.C., C.-H.C. and W.-K.C. All authors have read and agreed to the published version of the manuscript.

Funding

The work described in this paper was supported by a grant from the Research Grants Council of the Hong Kong Special Administrative Region, China for the project “A Study on Operating Positive Pressure Ventilator in Room Fires” (Project No. CityU 11212422).

Conflicts of Interest

The authors declare that there is no conflict of interest regarding the publication of this article.

References

  1. Ivanov, M.L.; Chow, W.K. Fire safety in modern indoor and built environment. Indoor Built Environ. 2023, 32, 3–8. [Google Scholar] [CrossRef]
  2. Chow, W.K.; Li, S.S.; Gao, Y.; Chow, C.L. Numerical studies on atrium smoke movement and control with validation by field tests. Build. Environ. 2009, 44, 1150–1155. [Google Scholar] [CrossRef]
  3. Chow, W.K. Performance of sprinkler in atria. J. Fire Sci. 1996, 14, 466–488. [Google Scholar] [CrossRef]
  4. Chow, W.K.; Gao, Y.; Zou, G.W.; Dong, H. Performance evaluation of sidewall long-throw sprinklers at height. In Proceedings of the 9th AIAA/ASME Joint Thermophysics and Heat Transfer Conference, San Francisco, CA, USA, 5–8 June 2006; Paper AIAA-2006-3288. American Institute of Aeronautics and Astronautics, Inc.: Reston, VA, USA, 2006. [Google Scholar]
  5. Yamada, T. Evaluation system of code equivalency for alternative design of fire protections system in Japan—Towards the intelligent fire protection system. In Proceedings of the Mini-symposium on Fire Safety Design of Buildings and Fire Safety Engineering, Tsukuba, Japan, 12 June 1995; Hasemi, Y., Hayashi, Y., Eds.; Building Research Institute, Ministry of Construction, Japan: Tokyo, Japan, 1995; pp. 15–23. [Google Scholar]
  6. Yeung, T.Y.; Chow, W.K. Study of positive pressure ventilation in room fires using a small-scale model. Heat Transf. Res. 2019, 50, 243–261. [Google Scholar] [CrossRef]
  7. Chow, C.L.; Chow, W.K.; Yuan, H.Y. A Preliminary Discussion on Selecting Active Fire Protection Systems for Atria in Green or Sustainable Buildings. Arch. Sci. Rev. 2004, 47, 229–236. [Google Scholar] [CrossRef]
  8. Zhu, J.; Li, W.; Lin, D.; Zhao, G. Study on Water Jet Trajectory Model of Fire Monitor Based on Simulation and Experiment. Fire Technol. 2019, 55, 773–787. [Google Scholar] [CrossRef]
  9. Chow, W.K. Necessity of in-depth evaluation of long-throw sprinkler installation at tall atria storing high amounts of combustibles. Int. J. Eng. Perform.-Based Fire Codes 2012, 11, 4–10. [Google Scholar]
  10. Wong, K.M.; Chow, W.K.; Cheng, A.C.H.; Wan, V.Y.; Chow, C.L. A study on positive pressure ventilator in room fires using small scale model. In Proceedings of the SFPE 19 Annual Conference & Expo, Phoenix, Arizona, 13–15 October 2019. [Google Scholar]
  11. Chow, C.L. A study on operating positive pressure ventilator in room fires. In GRF Research Project Funded by Research Grants Council of Hong Kong; Department of Architecture and Civil Engineering, City University of Hong Kong: Hong Kong, China, 2022. [Google Scholar]
  12. Cox, G. Combustion Fundamentals of Fire; Academic: London, UK; San Diego, CA, USA, 1995. [Google Scholar]
  13. Patankar, S.V. Numerical Heat Transfer and Fluid Flow; CRC Press: Boca Raton, FL, USA, 1980. [Google Scholar]
  14. Chow, W.K. Application of computational fluid dynamics for simulating building fires in subway system: Current situation. In Proceedings of the Third International Conference on Computational Methods in Tunnelling and Subsurface Engineering (EURO:TUN 2013), Bochum, Germany, 17–19 April 2013; Meschke, G., Eberhardsteiner, J., Schanz, T., Soga, K., Thewes, M., Eds.; ECCOMAS: Barcelona, Spain, 2013; pp. 701–712. [Google Scholar]
  15. Chow, C.L.; Chow, W.K. A brief review on applying computational fluid dynamics in building fire hazard assessment. In Fire Safety; Søgaard, I., Krogh, H., Eds.; Nova Science Publishers, Inc.: New York, NY, USA, 2009; Available online: https://www.novapublishers.com/catalog/product_info.php?products_id=9926 (accessed on 11 January 2022).
  16. Chow, W.K. Mistakes made in the application of computational fluid dynamics. In Hot Issues in Fire Engineering; Department of Building Services Engineering, The Hong Kong Polytechnic University: Hong Kong, China, 2013; Available online: https://www.academia.edu/67780106/ (accessed on 11 January 2022).
  17. Chow, W.K. Comments on Simulating Big Post-Flashover Room Fires Using Computational Fluid Dynamics; Engineering Archive: Menomonie, WI, USA, 2023. [Google Scholar]
  18. Zou, G.W.; Tan, H.P.; Chow, W.K.; Gao, Y. Effects of varying Smagorinsky constant on simulating post-flashover fires. Int. J. Comput. Fluid Dyn. 2007, 21, 107–119. [Google Scholar] [CrossRef]
  19. Brown, A.; Bruns, M.; Gollner, M.; Hewson, J.; Maragkos, G.; Marshall, A.; McDermott, R.; Mercie, B.; Rogaume, T.; Stoliarov, S.; et al. Proceedings of the first workshop organized by the IAFSS Working Group on Measurement and Computation of Fire Phenomena (MaCFP). Fire Saf. J. 2018, 101, 1–17. [Google Scholar] [CrossRef] [PubMed]
  20. Zeng, W.R.; Li, S.F. Review on chemical reactions of burning Poly(methyl methacrylate) PMMA. J. Fire Sci. 2002, 20, 401–433. [Google Scholar] [CrossRef]
  21. Yuen, W.W. The role of thermal radiation on the initiation of flashover in a compartment fire. Int. J. Heat Mass Transf. 2004, 47, 4265–4276. [Google Scholar] [CrossRef]
  22. Chow, W.K.; Han, S.S.; Du, W.F. ‘Bridge-mixing’ of gasified fuel vapours and simultaneous ignitions of different combustibles at flashover. J. Fire Sci. 2006, 24, 65–76. [Google Scholar] [CrossRef]
  23. Ivanov, M.; Chow, W.K.; Yue, T.K.; Tsang, H.L.; Peng, W. Upgrading of fire safety requirement for tall buildings in Bulgaria and proposal of implementing fire safety management under facility management. Facilities 2022, 40, 380–393. [Google Scholar] [CrossRef]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Chow, C.-L.; Cheng, C.-H.; Chow, W.-K. Active Firefighting Systems Against Flashover Fires in Big Halls. Fire 2024, 7, 486. https://doi.org/10.3390/fire7120486

AMA Style

Chow C-L, Cheng C-H, Chow W-K. Active Firefighting Systems Against Flashover Fires in Big Halls. Fire. 2024; 7(12):486. https://doi.org/10.3390/fire7120486

Chicago/Turabian Style

Chow, Cheuk-Lun, Chi-Honn Cheng, and Wan-Ki Chow. 2024. "Active Firefighting Systems Against Flashover Fires in Big Halls" Fire 7, no. 12: 486. https://doi.org/10.3390/fire7120486

APA Style

Chow, C. -L., Cheng, C. -H., & Chow, W. -K. (2024). Active Firefighting Systems Against Flashover Fires in Big Halls. Fire, 7(12), 486. https://doi.org/10.3390/fire7120486

Article Metrics

Article metric data becomes available approximately 24 hours after publication online.
Back to TopTop